This report was prepared by the Electromagnetics and Novel Applications Laboratory of the University of Cyprus within the framework of measuring and assessing the electric and magnetic field levels by AC power systems at the location of interest:
- Stadiou Street, Strovolos, 2058 Nicosia, in proximity to Substation “ZENIA ARTEMIS S/S GS2 4015”
The recorded measurements were compared to the reference levels described in the Council Recommendation of 12th July 1999 on the limitation of exposure of the general public to electromagnetic fields (0 Hz to 300 GHz), 1999/519/EC. Compliance with these recommended levels ensures that basic restrictions are respected. These reference levels are aligned with Cypriot legislation.
The measurement positions and maximum results per location are summarized in the table below.
|
Starting Point |
Measurement height (m) |
Magnetic field level (µT) |
Field quantity |
Frequency (Hz) |
ICNIRP General Public (%) |
|
Measuring point |
|||||
|
1. (Living Room) |
1 (above ground level) |
0.012 |
resultant magnetic field |
5 |
0.0008 |
|
2. (Kitchen) |
1 (above ground level) |
0.010 |
resultant magnetic field |
6 |
0.0009 |
|
3. (Master Bedroom) |
1 (above ground level) |
0.006 |
resultant magnetic field |
5 |
0.0004 |
|
4. (Bedroom_2) |
1 (above ground level) |
0.005 |
resultant magnetic field |
5 |
0.0003 |
|
5. (Bedroom_3) |
1 (above ground level) |
0.005 |
resultant magnetic field |
6 |
0.0004 |
Table 1: Maximum magnetic field measurement at the investigated area (apartment on the first floor).
The electromagnetic field measurements conducted at the location of interest were all below the recommended General Public reference levels of the National Exposure Limits as defined in Council Recommendation 1999/519/EC.
Last Updated on July 7, 2025