This report was prepared by the Electromagnetics and Novel Applications Laboratory of the University of Cyprus within the framework of measuring and assessing the electric and magnetic field levels by AC power systems at the location of interest:
- Substation “S/S KOTSONIS” located in the area of Aradippou, Larnaca. The measurements were conducted on 27/11/2024 from 10:30 a.m. to 11:30 a.m. in accordance with IEC 62110:2009.
More specifically, the evaluation of electromagnetic fields in the frequency range 5 Hz – 32 kHz was carried out using the NARDA EFA-300 Isotropic Field Analyser. Measurements were taken around the perimeter of the substation at a height of 1.0 m above ground. Additionally, further measurements were performed at specific points indicated on site (non-standardized measurements outside the IEC 62110:2009 procedures).
The recorded measurements were compared to the reference levels described in the Council Recommendation of 12th July 1999 on the limitation of exposure of the general public to electromagnetic fields (0 Hz to 300 GHz), 1999/519/EC. Respecting these recommended levels ensures that the basic restrictions are not exceeded. These reference levels are aligned with Cypriot legislation.
A summary of the low-frequency magnetic field results per measurement point is presented in the table below.
|
Measurement Point |
Measurement Height (m) |
Magnetic Field Level (µT) |
Frequency (Hz) |
ICNIRP General Public (%) |
|
1 |
1.0 |
0.023 |
42 |
0.019 |
|
2 |
1.0 |
0.022 |
18 |
0.008 |
|
3 |
1.0 |
0.043 |
27 |
0.023 |
|
4 |
1.0 |
0.018 |
33 |
0.012 |
|
5 |
1.0 |
0.018 |
15 |
0.005 |
|
6 |
1.0 |
0.019 |
17 |
0.007 |
|
7 |
1.0 |
0.016 |
22 |
0.007 |
|
8 |
1.0 |
0.016 |
13 |
0.004 |
|
9 |
1.0 |
0.016 |
6 |
0.001 |
|
10 |
1.0 |
0.063 |
45 |
0.057 |
|
11 |
1.0 |
0.065 |
50 |
0.065 |
|
12 |
1.0 |
0.065 |
41 |
0.053 |
|
13 |
1.0 |
0.036 |
12 |
0.009 |
|
14 |
1.0 |
0.037 |
13 |
0.009 |
|
15 |
1.0 |
0.036 |
9 |
0.006 |
Table 1: Maximum magnetic field measurement at the investigated area.
The magnetic field measurements conducted at the location of interest were below the recommended General Public reference levels of the National Exposure Limits as defined in Council Recommendation 1999/519/EC.