This report was prepared by the Electromagnetics and Novel Applications Laboratory of the University of Cyprus within the framework of measuring and assessing the electric and magnetic field levels by AC power systems at the location of interest:

  • Substation “EPTANISOU S/S GS2 3288” located in the area of Engomi, Nicosia.
    The measurements were conducted on 13/11/2024 from 11:00 a.m. to 11:50 a.m. in accordance with IEC 62110:2009.

More specifically, the evaluation of electromagnetic fields in the frequency range 5 Hz – 32 kHz was carried out using the NARDA EFA-300 Isotropic Field Analyser. Measurements were performed around the perimeter of the substation at a height of 1.0 m above the ground. Additional point measurements were also taken at locations indicated at the site of interest (non-standardized measurements outside the IEC 62110:2009 scope).

The recorded measurements were compared to the reference levels described in the Council Recommendation of 12th July 1999 on the limitation of exposure of the general public to electromagnetic fields (0 Hz to 300 GHz), 1999/519/EC. Respecting these recommended levels ensures that the basic restrictions are not exceeded. These reference levels are harmonized with Cypriot legislation.

A summary of the low-frequency magnetic field results per measurement point is presented in the table below.

Measurement Point Measurement Height (m) Magnetic Field Level (µT) Frequency (Hz) ICNIRP General Public (%)
1 1.0 0.018 5 0.001
2 1.0 0.020 50 0.020
3 1.0 0.018 40 0.014
4 1.0 0.012 6 0.001
5 1.0 0.011 11 0.002
6 1.0 0.010 7 0.001
7 1.0 0.014 10 0.003
8 1.0 0.010 8 0.002
9 1.0 0.009 6 0.001
10 1.0 0.019 7 0.002
11 1.0 0.010 6 0.001

Table 1: Maximum magnetic field measurement at the investigated area.

The magnetic field measurements conducted at the location of interest were below the recommended General Public reference levels of the National Exposure Limits as defined in Council Recommendation 1999/519/EC.

 